Weil-McLain · Boiler troubleshooting

Recheck maximum and minimum CO2 and CO after adjustment

ECO Tec Series 3

What is going on

Confirm both firing rates after any gas valve change.

Check in this order

  1. Turn the boiler off, then back on, and put it in Test Mode at maximum. Confirm CO2 is unchanged and CO is within limits.
  2. Reduce to minimum and recheck CO2 and CO.
  3. If CO2 and CO cannot be reached, contact your WM Technologies representative.
  4. Replace the test port cap (A).

Applies to: ECO Tec Series 3 80/110/150/199

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ECO Tec Series 3 Condensing Gas Boiler Boiler Manual, p. 136. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.