Weil-McLain · Boiler troubleshooting
Thermostat, DHW sensor and anticipator wiring
What is going on
Default input terminals and wiring precautions for thermostats and DHW tank control.
Check in this order
- For default operation, connect the space heating thermostat to terminal strip P15, terminals 1 and 2.
- For default DHW operation, connect the DHW tank temperature control across terminal strip P11, terminals 4 and 5.
- Install thermostats on inside walls away from drafts, water pipes, lights, TV, sun and fireplaces.
- If the thermostat connects directly to the boiler, set its anticipator to 0.1 A.
- If it connects to relays or other devices, set the anticipator to match the total power draw of those devices.
- Use isolating relays with 3-wire zone valves to prevent stray voltage damage and nuisance problems.
Applies to: Ultra U-Control heat demand inputs
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain Ultra Series 4 boiler manual, p. 95. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.