NTI · Boiler troubleshooting
Replace the fan and mixer
What is going on
The fan and mixer on the TRX150 come off as one assembly, and that is how I usually do it. The thing that bites people is the fuel setup. The gas diaphragm and mixer are different for natural gas and propane, and a mismatch gives you bad combustion, rough starts or a lockout. Most fan jobs go wrong at reassembly, either a pinched O-ring or a missing gasket, which leaks and throws the combustion off.
Likely causes
- Failed fan or noisy bearings after years of running
- Fan not reaching speed, giving blocked or low airflow errors
- Damaged mixer O-ring leaking air or gas
- Wrong gas diaphragm or mixer for the fuel type after a swap
Check in this order
- Turn off power and shut the gas supply before starting.
- Remove the silencer and gas line.
- Loosen the three screws holding the mixer to the fan. Check the O-ring is not damaged and replace it if it is.
- Loosen the three screws holding the fan to the heat exchanger.
- Reassemble the mixer and fan in reverse order with the O-ring between them.
- Reinstall the fan and combustion assembly and fit the gasket between the fan and air inlet channel.
- Confirm the gas diaphragm and mixer match the fuel (natural gas or propane).
- Leak-check the gas connection, then verify combustion with an analyzer. Gas work is for a licensed technician.
Applies to: TRX150
More boiler guides
Related
NTI error codes · NTI parts · NTI tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: NTI TRX150 manual, p. 99. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.