Navien · Boiler troubleshooting
Leak testing the common vent
What is going on
Test every joint on the common vent before the boiler is put into service.
Check in this order
- Assemble the wye joint or wye assembly to the vent pipe with solvent cement on mating surfaces.
- Fill the system with water and turn the boiler on.
- Check every joint with a bubble test kit.
- If bubbles form, repair that section of pipe and bubble test it again.
Applies to: NCB700-190/060, NCB700-190/080, NCB700-240/110, NCB700-240/130, NCB700-250/150
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NCB700 installation and operation manual, p. 99. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.