Viessmann · Boiler troubleshooting

Check the fixed high limit (FHL)

Vitotronic 100 GC1

What is going on

Test of the fixed high limit on the Vitotronic 100. The adjustable high limit is bypassed during the test.

Check in this order

  1. Hold down the TÜV test button during the test (in the h position). A minimum supply rate must be present.
  2. Make sure the boiler flow rate is at least 10% of the boiler flow rate at rated output.
  3. Reduce the heat consumption as far as possible. The adjustable high limit R is now bypassed.
  4. Let the burner run until the boiler water reaches the safety temperature and the fixed high limit switches OFF.
  5. After the burner is shut down by the fixed high limit, release the TÜV button. Fault D4 appears on the display.
  6. Wait until the boiler water is 15 to 20 °C (25 to 35 °F) below the set safety temperature.
  7. Reset the fixed high limit by pressing button E. Fault D4 clears from the display.

Applies to: Vitotronic 100 GC1

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitotronic 100 / Vitocontrol-S installation and service instructions, p. 91. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.