Shut down boiler before cleaning the heat exchanger (pin side)
What is going on
Prepare the boiler before opening the heat exchanger for cleaning.
Check in this order
- Follow the 'To Turn Off Gas to Appliance' instructions on the boiler and the lighting instructions.
- Do not drain the boiler unless it will be exposed to freezing. If freeze prevention fluid is in the system, do not drain.
- Let the boiler cool to room temperature if it has been firing.
- Turn the two rotary latches on the front door, tilt the top of the door forward, then lift it up.
- Use a 13 mm wrench or socket to remove the nuts on the front cover plate and remove the plate.
- Use the cleanout plug in the flue pipe to rinse debris into the condensate drain. Flush the condensate drain, then refill it.
- Follow the heat exchanger access and cleaning procedure.
Applies to: SlimFit SF-550 and SF-750 Series 3
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SlimFit series3 commercial gas-fired water boiler boiler manual, p. 105. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.