WMCR circulator zone controller plus boiler-controlled DHW

SlimFit Series 2

What is going on

DHW is piped directly to the boiler. The zone controller calls for space heating on INPUT 2. A relay with a normally closed contact interrupts the zone controller's ZC-ZR 120 VAC circuit during DHW operation so space heating stops while DHW runs.

Check in this order

  1. Provide relay R1 with a 120 VAC coil and an NC contact.
  2. Wire R1 to interrupt the zone controller's ZC-ZR 120 VAC operating circuit.
  3. Connect the zone controller call for heat (X-X) to INPUT 2 and keep INPUT 2 on PRIORITY 2.
  4. Wire the DHW aquastat to INPUT 1 and assign INPUT 1 to PRIORITY 1.
  5. Wire the DHW circulator to OUTPUT 1.
  6. Set the heating system type in PRIORITY 2 as required.

Applies to: SF1000L/R, SF1500L/R, SF2000L/R

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SlimFit Series 2 Boiler Manual 550-100-561/1225, p. 60. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.