Zone valve zoning, primary/secondary piping (with optional DHW)

SVF Series 1

What is going on

Boiler loop is a secondary circuit off the primary system loop. This ensures flow in the boiler loop and keeps the boiler circulator head off the zone valves.

Check in this order

  1. Install a system circulator sized for the required flow and head.
  2. Install a flow/check valve on the boiler outlet piping to stop gravity circulation during DHW heating.
  3. Use at least the minimum pipe size from Figure 11 on all boiler loop piping.
  4. Keep primary/secondary tees no more than 8 pipe diameters apart.
  5. Place system supply and return immersion sensors at least 6 pipe diameters (no more than 3 feet) from the boiler connection tees.
  6. Wire zone valve end switches to a Space Heating Priority input (default Priority 2).
  7. Use isolation relays if connecting 3-wire zone valve end switches to the inputs.
  8. Provide a system expansion tank per page 16. Do not use a closed-type tank if connecting to a water heater with an automatic vent.

Applies to: SVF 1500-3000 Series 1

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SVF Series 1 boiler manual, p. 17. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.