Service work to be done at least once a year by a qualified heating contractor. Any deficiencies must be corrected immediately.
Check in this order
- Test the safety high limits for correct function.
- Test the burner and its accessories per the burner maintenance checklist.
- Test and establish correct chemical makeup of the system water.
- Check the flue pipe, chimney connection and chimney.
- Check the pressure relief valve and system pressure.
- Check heating pipe joints, valves and air vents for leaks and correct any leaks immediately.
- Check combustion air supply and ventilation of the boiler/mechanical room.
- Check that no combustible materials or chemicals are stored too close to the boiler.
- Test high limits by dialing lower settings and switching the burner on and off.
- If a low water cut-off is installed, check it per the manufacturer's instructions.
- If the circulating pump is field-installed or existing, check its maintenance or lubrication requirements per the manufacturer's specifications.
- Check the gas piping, unions, gas valve and manifold for gas-tight connections.
- Check ignition and burner operation.
- Perform a combustion test.
Applies to: Vitocrossal 200 CM2 186 to 620
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 200 CM2 operating instructions, p. 10-11. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.