Viessmann · Boiler troubleshooting

Annual heating contractor service

Vitocrossal 200 CM2

What is going on

Service work to be done at least once a year by a qualified heating contractor. Any deficiencies must be corrected immediately.

Check in this order

  1. Test the safety high limits for correct function.
  2. Test the burner and its accessories per the burner maintenance checklist.
  3. Test and establish correct chemical makeup of the system water.
  4. Check the flue pipe, chimney connection and chimney.
  5. Check the pressure relief valve and system pressure.
  6. Check heating pipe joints, valves and air vents for leaks and correct any leaks immediately.
  7. Check combustion air supply and ventilation of the boiler/mechanical room.
  8. Check that no combustible materials or chemicals are stored too close to the boiler.
  9. Test high limits by dialing lower settings and switching the burner on and off.
  10. If a low water cut-off is installed, check it per the manufacturer's instructions.
  11. If the circulating pump is field-installed or existing, check its maintenance or lubrication requirements per the manufacturer's specifications.
  12. Check the gas piping, unions, gas valve and manifold for gas-tight connections.
  13. Check ignition and burner operation.
  14. Perform a combustion test.

Applies to: Vitocrossal 200 CM2 186 to 620

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 200 CM2 operating instructions, p. 10-11. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.