Viessmann · Boiler troubleshooting
System version 7: Vitocrossal 300 lead boiler with Vitorond 200 lag boiler and shunt pump return control
What is going on
Vitocrossal 300 (CT3) is the lead boiler and Vitorond 200 (VD2) is the lag boiler, run by a Viessmann outdoor-reset cascade control with modulating boiler water temperature. The CT3 has two return connections: circuits with the higher return temperature go to the upper connection, lower-temperature circuits go to the lower connection, and at least 15% of rated output must be on the lower connection. Return temperature control on the Vitorond uses the shunt pump and an isolation valve. Sensor T1 controls the isolation valve and sensor T2 switches the shunt pump. The LON-BUS sets the boiler supply temperature from the highest mixing-circuit demand plus an adjustable differential.
Check in this order
- Connect at least 15% of rated output to the lower return connection on the Vitocrossal 300.
- Place sensor T1 to control the isolation valve and sensor T2 to switch the shunt pump, as shown in the system diagram.
Applies to: System version 7 (lead Vitocrossal 300 CT3, lag Vitorond 200 VD2)
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 100 GC1 and Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 24. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.