Closed-type expansion tank piping
What is going on
Air is in direct contact with the tank water in this layout. Never use an automatic air vent with a closed-type tank, because it removes air and water-logs the tank.
Likely causes
- Automatic air vent fitted to a closed-type tank system
- Leaks in system or tank piping
Check in this order
- Run ½" or ¾" piping from the air separator outlet to the tank fitting.
- Slope horizontal piping at least 1 inch per 5 feet.
- Use a tank fitting such as B&G Tank-trol or Taco Taco-trol to control gravity flow and set fill height.
- Do not install an automatic air vent in this system.
- Correct all leaks in the system or tank piping.
- Fill the tank per the tank maker's instructions.
Applies to: Closed-type expansion tank (Figure 67)
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: ECO Tec Series 3 boiler manual, p. 58. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.