Weil-McLain · Boiler troubleshooting
Priority timing: MAX ON TIME and MIN ON TIME
What is going on
Each priority has its own settings. MAX ON TIME limits how long a priority runs before a lower priority's call takes over. MIN ON TIME is the shortest time a priority runs before a higher priority or the next lower priority can take over. Multiple inputs on the same priority run together when active. The boiler circulator output can be set per priority, and Blr Circ should be OFF for DHW piped directly with its own DHW circulator.
Check in this order
- Use PRIORITY 1 for DHW when a DHW system is connected.
- Set MAX ON TIME and MIN ON TIME for each priority in the Wizard Priority Switching step or the priority menu.
- Set Blr Circ to OFF for DHW piped directly with its own DHW circulator.
Applies to: SF1000L/R, SF1500L/R, SF2000L/R
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SlimFit Series 2 Boiler Manual 550-100-561/1225, p. 63. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.