Room air installation sequence
What is going on
Install room air combustion air and exhaust with the room air screen, as required for the site.
Check in this order
- Remove and discard the screw from the combustion air vent connection.
- Remove and discard the combustion air vent cap.
- Install the combustion air vent pipe, make sure it is seated, and secure it with the supplied screw.
- Place the vent screen inside the elbow and secure it with the supplied screw. Use the room air screen where room air is dusty.
- Install the exhaust vent pipe, make sure it is seated, and secure it to the exhaust adapter ring with the supplied screw.
Applies to: Room air venting
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 44. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.