Water side connections and flow protection

Vitorond 200 VD2

What is going on

The boiler is only for forced circulation hot water systems. Connect supply and return headers and safety piping while keeping air venting and check valve requirements in mind.

Check in this order

  1. Thoroughly flush the heating system, especially when retrofitting to an existing system.
  2. Install the supply and return headers and make all heating system connections.
  3. Install a spring-loaded flow check valve just downstream of the circulation pump in the heating supply. This helps stop water flowing into space heating circuits during DHW priority or summer operation.
  4. Do not install an isolation valve between the boiler and the safety header.
  5. Route the discharge pipe so it cannot scald people.
  6. Remove air with air vents and avoid piping that can trap air.
  7. Meet all requirements in the System Design Guidelines and Technical Data Manual.
  8. Install the safety piping.

Applies to: Vitorond 200 VD2 320 to 1080

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitorond 200, VD2 Series 320 to 1080 Installation Instructions, p. 20. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.