Viessmann · Boiler troubleshooting

Boiler temperature control sequence

Vitotronic 100 GC1

What is going on

The boiler water temperature is controlled by a two-stage or modulating burner. The set point comes from Vitocontrol-S. Three sensors monitor the boiler water: the fixed high limit (110 C, adjustable to 99 C), the adjustable high limit (95 C, adjustable to 87 or 100 C) and the boiler temperature sensor KTS. The electronic maximum limit can be set from 20 to 127 C (68 to 261 F) via coding 06.

Check in this order

  1. The burner starts when the boiler is 2 C (3.6 F) below the calculated set point.
  2. The burner may be delayed a few minutes depending on connected auxiliary equipment and fuel type.
  3. The burner switches off at the switch-off differential set in coding 13.

Applies to: Vitotronic 100 GC1 boiler temperature control

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocontrol-S VD2/CT3/CM2 installation and service manual, p. 123. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.