Pre-test checks before high limit safety cut-out test (CSD-1)

Vitocrossal 200 CI2

What is going on

Checks to make before testing the boiler high limit controls. Viessmann says the high limit is set at a fixed 210°F (99°C) and needs a manual reset after it trips.

Check in this order

  1. Check the heating system pressure. Operating range is 15 psi (1.0 bar) minimum to 80 psi (5.5 bar) maximum.
  2. For room air dependent operation, confirm the combustion air openings in the mechanical room are open.
  3. For room air independent direct vent operation, confirm the air pipes are unobstructed.
  4. Check the gas supply pressure against the target value in the table on page 24.
  5. Open the gas line shut-off valves.
  6. Check the neutralizing system, if installed, including the hydraulic seal in the condensate trap.
  7. Check all gaskets and plugs and retighten if needed.
  8. Check heating water side connections for leaks after about 500 hours of run time.
  9. Switch on the boiler power at the breaker, then power on the control unit.

Applies to: Vitocrossal 200 CI2 gas condensing boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 200 CI2 Service Instructions, p. 10. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.