Viessmann · Boiler troubleshooting

Installing the boiler panels

Vitocrossal 300 CA3B Dual Fuel

What is going on

Panel reinstallation order after service.

Check in this order

  1. Install the top front cover plate with 4 screws.
  2. Install the lower front cover plate.
  3. Install the top front panel.
  4. Insert the bottom of the lower front panel in place and push it into place.
  5. Install the top left side and bottom left side panels.
  6. Slide the top panels toward the left side.
  7. Install the top right side panels.
  8. Install with screws to the right side of the top panels.

Applies to: Vitocrossal 300 CA3B Dual Fuel 2.5 to 6.0

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 300 Dual Fuel CA3B service instructions, p. 49. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.