Weil-McLain · Boiler troubleshooting

Check blower speeds at low, ignition and high fire

Ultra Series 4

What is going on

Run manual test mode at each firing rate and compare blower RPM to Figure 121. Enable high altitude only above 5,500 ft.

Likely causes

  • Blower or control setting out of range
  • Wrong altitude setting

Check in this order

  1. For altitudes above 5,500 ft, enable high altitude in the boiler setup menu; below 5,500 ft leave it off.
  2. Go to Manual test mode on the U-Control (see Figure 115, page 102).
  3. Set the firing rate to MINIMUM (low fire). Record the RPM; it must be no less than the minimum setting and no higher than the ignition factory setting.
  4. Set the firing rate to MEDIUM (ignition). Record RPM; it must be within 200 RPM of the Figure 121 value.
  5. Set the firing rate to MAXIMUM (high fire). Record RPM; it must be within 200 RPM of the Figure 121 value.
  6. If any value is outside these ranges, contact the factory for technical assistance.

Applies to: Ultra 80, 105, 155, 230, 299, 399

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Ultra Series 4 gas-fired water boiler manual, p. 113. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.