Popping or percolating noise in boiler

CGaCGiEGPEGLGB Series 2LGB Series 3

What is going on

Noise from mineral scale in sections, often from constant makeup water or wrong water pH.

Likely causes

  • Mineral deposits in sections from constant makeup water
  • Incorrect boiler water pH
  • Insufficient water flow through boiler

Check in this order

  1. Have a qualified service technician de-lime the boiler if necessary; very heavy deposits may not come off by de-liming
  2. Have a qualified service technician repair leaks so makeup water is no longer needed
  3. Have a qualified service technician check and correct pH; keep it between 7.0 and 8.5
  4. Check all valves to and from the boiler and return them to the proper setting
  5. Confirm the circulator is correctly sized

Applies to: All listed CGa, CGi, EG, PEG and LGB boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain CGa, CGi, EG, PEG & LGB user manual, p. 9. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.