Weil-McLain · Boiler troubleshooting

Zoning with circulators: three zones plus Indirect DHW

ECO Tec Series 3

What is going on

Three space heating zones plus an Indirect DHW tank piped directly to the boiler. Shown for Heating Only models.

Check in this order

  1. Wire the DHW aquastat to INPUT 1 and assign INPUT 1 to PRIORITY 1.
  2. Wire the zone thermostats to INPUT 3 and INPUT 4 and the other space heating input as shown.
  3. Wire circulators to Outputs 2, 3 and 4 (2.2 A max each).
  4. Set the space heating priority (PRIORITY 2) to the heating system type during the WIZARD or in System Settings.
  5. Use the factory default settings for DHW and the heating system type, or change them if needed.
  6. On Combi models, Input/Output pairs 1 and 4 are used for the 3-way valve and cannot be used for other purposes.

Applies to: ECO Tec Series 3 Heating Only models

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ECO Tec Series 3 boiler manual, p. 75. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.