Viessmann · Boiler troubleshooting
Flow switch test
What is going on
The boiler has a flow sensing device. If flow is too low, the switch opens, the burner shuts down and it will not restart until adequate flow returns.
Check in this order
- Throttle the water flow to or from the boiler.
- Confirm the boiler shuts down once flow drops below its safe operating set point.
- Restore flow and confirm the burner restarts.
Applies to: Vitodens 200 B2HA/B2HB boilers with flow switch
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 200-W B2HB Service Instructions, p. 8. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.