Viessmann · Boiler troubleshooting

Flow switch test

Vitodens 200-W

What is going on

The boiler has a flow sensing device. If flow is too low, the switch opens, the burner shuts down and it will not restart until adequate flow returns.

Check in this order

  1. Throttle the water flow to or from the boiler.
  2. Confirm the boiler shuts down once flow drops below its safe operating set point.
  3. Restore flow and confirm the burner restarts.

Applies to: Vitodens 200 B2HA/B2HB boilers with flow switch

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 200-W B2HB Service Instructions, p. 8. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.