Weil-McLain · Boiler troubleshooting

Low-temperature system: system-bypass piping valve setup

CGi Series 5

What is going on

Keeps return water to the boiler at 130°F or higher on converted gravity or large-water-content systems. Not for radiant heating, because it gives no control of the water temperature sent to the tubing. Can cause uneven heat if system flow is reduced too much.

Check in this order

  1. Start with valve 7a fully closed and valve 7b fully open.
  2. Slowly open valve 7a while closing valve 7b until gauge 8 reads at least 130°F at all times.
  3. Set the valves with the system at its coldest expected temperature (60°F for converted gravity or high-mass radiant systems).
  4. Valve 7b may need to be slightly closed on low pressure drop systems so enough flow goes through valve 7a.
  5. Pipe the boiler circulator as shown; it cannot be used as one of the zoning circulators.

Applies to: CGi-25 to CGi-8 converted gravity or steam systems (Figure 23)

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain CGi Series 5 boiler manual, p. 36. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.