Handling ceramic fiber sight glass gasket

SlimFit Series 2

What is going on

The sight glass gasket contains ceramic fibre that can release respirable silica dust. Keep the gasket wet while removing it.

Likely causes

  • Dry removal releasing airborne fibre dust

Check in this order

  1. Wear an N95 respirator, long sleeves, gloves and eye protection.
  2. Wet the gasket with water to stop airborne dust.
  3. Remove the gasket and seal it in a plastic bag for disposal.
  4. Wash contaminated clothing separately and rinse the washer.
  5. If eye contact occurs, irrigate immediately. If breathing is affected, move to fresh air.

Applies to: SlimFit Series 2 sight glass gasket

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SlimFit Series 2 boiler manual 550-100-561/1225, p. 87. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.