Zone valve zoning, high flow or high head DHW circuits

SVF 500/600 Series 1

What is going on

Use when DHW circuit flow exceeds boiler limits or when a coil-type DHW tank has high pressure drop. DHW water flows only through the secondary connection piping. Size the connection piping for the total flow it must carry.

Check in this order

  1. Size the DHW secondary connection piping (item 23) for the total flow.
  2. Install a system circulator that delivers the required flow and head.
  3. Install the flow/check valve on the boiler outlet piping to prevent gravity circulation during DHW heating.
  4. Keep connection tees no more than eight pipe diameters apart.

Applies to: DHW zone valve piping

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SVF 500/600 Series 1 boiler manual, p. 24. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.