Water quality and scale prevention

Vitocrossal 200 CI2

What is going on

Hard water causes scale on the heat exchanger. Soften fill and top-up water where the alkaline earth content exceeds the standard value or where large top-up volumes are expected. Fill only with fully softened water.

Likely causes

  • Hard fill or top-up water
  • Large top-up volumes from leaks or repairs

Check in this order

  1. Test the fill water if there is any doubt about hardness.
  2. Soften the fill and top-up water when the hardness exceeds the table limit or top-up volumes are high.
  3. In systems over 170 MBH (50 kW), install a water meter on the fill line.
  4. Record fill volume and water hardness on the maintenance checklist.
  5. If the system is not filled with fully softened water, start the system with high flow, starting at the lowest boiler output.
  6. In multi-boiler systems, start all boilers at the same time.
  7. Treat the first fill and any later fill, top-up or expansion before start-up where water treatment is required.

Applies to: All heating water circuits

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 200 CI2 service instructions, p. 94. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.