Water quality and scale prevention
What is going on
Hard water causes scale on the heat exchanger. Soften fill and top-up water where the alkaline earth content exceeds the standard value or where large top-up volumes are expected. Fill only with fully softened water.
Likely causes
- Hard fill or top-up water
- Large top-up volumes from leaks or repairs
Check in this order
- Test the fill water if there is any doubt about hardness.
- Soften the fill and top-up water when the hardness exceeds the table limit or top-up volumes are high.
- In systems over 170 MBH (50 kW), install a water meter on the fill line.
- Record fill volume and water hardness on the maintenance checklist.
- If the system is not filled with fully softened water, start the system with high flow, starting at the lowest boiler output.
- In multi-boiler systems, start all boilers at the same time.
- Treat the first fill and any later fill, top-up or expansion before start-up where water treatment is required.
Applies to: All heating water circuits
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 200 CI2 service instructions, p. 94. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.