Viessmann · Boiler troubleshooting

Field test of fixed high limit (CSD-1)

Vitodens 200-W B2HA

What is going on

Where required by law, the fixed high limit can be tested in the field. The manufacturer is not responsible for damage caused by overheating during this test. The fixed high limit trips a fault that needs a manual reset.

Check in this order

  1. Simulation #1: close the boiler valve and jumper across the flow switch.
  2. Simulation #1: run the boiler at high fire. In B2TB models set coding address 06 to maximum. The burner shuts down on the coding card but the temperature keeps rising until the fixed high limit trips.
  3. Simulation #1: once the fixed high limit trips, slowly open the boiler valve to cool the boiler.
  4. Simulation #2: throttle the boiler valve so the burner runs with as little flow as possible.
  5. Simulation #2: run the boiler to high fire using the relays test.
  6. Simulation #2: when the burner shuts down on the electronic limit, close the ball valve to stop the flow.
  7. Simulation #2: the temperature should keep rising until the fixed high limit trips. Then slowly open the boiler valve to cool down.
  8. Simulation #3: remove one wire from the limit switch. This creates a fault that requires manual reset.

Applies to: Vitodens 200-W B2HA 19, 28, 35

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitodens 200-W B2HA service instructions, p. 8. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.