Weil-McLain · Boiler troubleshooting

Install relief valve and discharge piping

SlimFit Series 3 Commercial

What is going on

The relief valve mounts on the 3/4 inch nipple in the supply tee. Discharge piping must be safe and clear.

Check in this order

  1. Install the female relief valve on the 3/4 inch nipple in the 2x3/4 inch bushing of the supply tee. Use pipe no smaller than 3/4 inch.
  2. Pipe the discharge to a safe disposal point.
  3. Keep the discharge line as short as possible and the same size as the valve outlet along its full length.
  4. Slope the discharge line down from the valve and end it at least 6 inches above a floor drain where discharge is visible.
  5. End the line plain (not threaded) and use material rated for 375 °F or higher.
  6. Do not route the discharge where it can freeze. Do not install any shutoff valve between the valve and boiler or in the discharge line.
  7. After filling and pressurizing, lift the lever to test. Confirm it discharges freely and replace it if it does not.

Applies to: All SlimFit boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SlimFit 550/750 Series 3 boiler manual, p. 11-12. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.