Viessmann · Boiler troubleshooting
Install valve adaptor for boiler return mixing or modulating valve
What is going on
Wiring a 120V or 24V valve actuator through the valve adaptor.
Check in this order
- Disconnect power to the control.
- Mount the 120V or 24V valve adaptor on the DIN rail inside the connection enclosure.
- Insert plug gS into socket gS on the control.
- Secure the cable with a tie.
- Connect the black adaptor wire to the aBH connection on the DIN rail (VD2: terminal 8, 9 or 10; CM2: 120V L out, terminal 10, 11 or 12).
- Connect the valve actuator wires to the adaptor terminals as shown in the figures.
Applies to: VD2/VD2A/CT3 and CM2 valve adaptors
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitotronic 100 GC1 / Vitocontrol-S VD2/CT3/CM2 installation and service instructions, pp. 47-48. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.