Replacing a boiler on an existing common vent

Ultra Series 4

What is going on

The Ultra cannot share a common vent with any other appliance. The old vent may be oversized for the appliances that remain on it, so test them before finishing the job.

Likely causes

  • Old vent sized for the removed boiler plus remaining appliances
  • Vent may be too large for the remaining appliances once the old boiler is removed

Check in this order

  1. Inspect the existing vent for correct size, horizontal pitch, blockage, leakage, corrosion or other defects.
  2. Close building doors and windows and doors to other spaces. Run clothes dryers, non-vented appliances and exhaust fans (range hoods, bath fans) at full speed. Do not run a summer exhaust fan. Close fireplace dampers.
  3. Run each remaining appliance alone with the others off. Set its thermostat so it runs continuously.
  4. After 5 minutes of main burner operation, check the draft hood relief opening for spillage with a flame, candle or smoke.
  5. Return doors, windows, fans and dampers to normal. If the vent fails, correct it to the National Fuel Gas Code (ANSI Z223.1 or B149.1/B149.2 in Canada), typically by resizing toward the minimum size from the code tables.

Applies to: Any Ultra boiler replacing a boiler on a shared chimney or common vent

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain Ultra Series 4 boiler manual, p. 16. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.