Viessmann · Boiler troubleshooting

Startup fault: fault indicator on and display flashing

Vitocrossal 300 CA3B Dual Fuel

What is going on

If the fault indicator lights during commissioning and the burner control display flashes, the section has likely lost gas, most often from air in the supply line.

Likely causes

  • Insufficient gas in the supply line
  • Air in the gas line

Check in this order

  1. Press the reset button R on the burner control unit.
  2. If the fault persists, purge the gas supply lines again with an approved gas purge burner or vent outdoors.
  3. Reset the burner control unit again.

Applies to: Vitocrossal 300 CA3B Dual Fuel boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 service instructions, p. 18. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.