Viessmann · Boiler troubleshooting

Clean condensate drain pipe and condensate trap

Vitocrossal 200 CI2

What is going on

Clean the inside of the condensate drain pipe and condensate trap at least once a year.

Likely causes

  • Deposits building up in the condensate trap or drain pipe

Check in this order

  1. Disconnect the condensate drain pipe to the neutralizing system from the condensate trap.
  2. Unscrew the lower part of the condensate trap. Remove the float and deposits, then clean the components.
  3. Reassemble the condensate trap.
  4. Refit the condensate drain pipe.
  5. If needed, clean the neutralizing system per the manufacturer's instructions.
  6. Confirm the condensate drains freely before operating the boiler.

Applies to: Vitocrossal 200 CI2 boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 200 CI2 Service Instructions, p. 32. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.