Clean condensate drain pipe and condensate trap
What is going on
Clean the inside of the condensate drain pipe and condensate trap at least once a year.
Likely causes
- Deposits building up in the condensate trap or drain pipe
Check in this order
- Disconnect the condensate drain pipe to the neutralizing system from the condensate trap.
- Unscrew the lower part of the condensate trap. Remove the float and deposits, then clean the components.
- Reassemble the condensate trap.
- Refit the condensate drain pipe.
- If needed, clean the neutralizing system per the manufacturer's instructions.
- Confirm the condensate drains freely before operating the boiler.
Applies to: Vitocrossal 200 CI2 boilers
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 200 CI2 Service Instructions, p. 32. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.