Rinnai · Boiler troubleshooting

Test the ignition safety shutoff device

I-Series Plus

What is going on

Simulates a flame loss by disconnecting the flame rod. The boiler should lock out with code 110 after the last start-up attempt.

Check in this order

  1. Make sure the boiler is not firing and the flame rod is not hot.
  2. Remove the boiler front panel.
  3. Disconnect the wiring connection from the left side flame rod under the burner. Do not touch the inside of the connector.
  4. Call for heat or turn on a DHW fixture to start the boiler.
  5. Confirm the boiler makes one start-up attempt and several restart attempts, then locks out with code 110 and the gas valve shuts off.
  6. Reconnect the flame rod wiring, press the DHW button to reset, and replace the front panel.

Applies to: All I-Series Plus condensing combi boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Rinnai I-Series Plus Condensing Combi Boiler Manual, p. 123. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.