Rinnai · Boiler troubleshooting
Test the ignition safety shutoff device
What is going on
Simulates a flame loss by disconnecting the flame rod. The boiler should lock out with code 110 after the last start-up attempt.
Check in this order
- Make sure the boiler is not firing and the flame rod is not hot.
- Remove the boiler front panel.
- Disconnect the wiring connection from the left side flame rod under the burner. Do not touch the inside of the connector.
- Call for heat or turn on a DHW fixture to start the boiler.
- Confirm the boiler makes one start-up attempt and several restart attempts, then locks out with code 110 and the gas valve shuts off.
- Reconnect the flame rod wiring, press the DHW button to reset, and replace the front panel.
Applies to: All I-Series Plus condensing combi boilers
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Rinnai I-Series Plus Condensing Combi Boiler Manual, p. 123. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.