Viessmann · Boiler troubleshooting

Annual service: safety, controls and water system checks

Vitorond 200 VD2A

What is going on

Annual checks by the heating contractor covering high limits, low water cut-off, pressure relief, water quality and the door switch.

Check in this order

  1. Test the safety high limits.
  2. Test the high limits by setting them lower and switching the burner on and off to confirm they work.
  3. Test the low water cut-off and verify it operates per the manufacturer's instructions.
  4. Check and flush the low water cut-offs (float type) during operation, following the supplier's instructions.
  5. Check the pressure relief valve and system pressure, and verify the automatic feed if installed.
  6. Test and establish the proper chemical makeup of the system water.
  7. Check the heating pipe joints, valves and air vents; correct any leaks immediately and find the cause.
  8. Make sure the door safety switch operates properly.
  9. If a circulating pump is field-installed or already present, check its maintenance or lubrication requirements per the pump manufacturer.

Applies to: VD2A-125 to VD2A-270

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitorond 200 VD2A service instructions, p. 16. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.