Viessmann · Boiler troubleshooting
Annual service: safety, controls and water system checks
What is going on
Annual checks by the heating contractor covering high limits, low water cut-off, pressure relief, water quality and the door switch.
Check in this order
- Test the safety high limits.
- Test the high limits by setting them lower and switching the burner on and off to confirm they work.
- Test the low water cut-off and verify it operates per the manufacturer's instructions.
- Check and flush the low water cut-offs (float type) during operation, following the supplier's instructions.
- Check the pressure relief valve and system pressure, and verify the automatic feed if installed.
- Test and establish the proper chemical makeup of the system water.
- Check the heating pipe joints, valves and air vents; correct any leaks immediately and find the cause.
- Make sure the door safety switch operates properly.
- If a circulating pump is field-installed or already present, check its maintenance or lubrication requirements per the pump manufacturer.
Applies to: VD2A-125 to VD2A-270
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitorond 200 VD2A service instructions, p. 16. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.