Viessmann · Boiler troubleshooting
Connect several remote control units with other BUS participants (Version 2)
What is going on
Remote controls and additional KM BUS participants are connected through an on-site terminal box.
Check in this order
- Install a terminal box on site.
- Connect the control unit to the terminal box.
- Connect the remote control units and the further BUS participants through the terminal box, following the diagram.
- Keep each branch to the terminal box to a maximum of 15 m / 50 ft.
- Keep the total length of all KM BUS cables to a maximum of 50 m / 164 ft.
Applies to: Several remote controls plus additional KM BUS participants
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 300, Model GW2 installation and service instructions, p. 111. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.