Connect several remote control units with other BUS participants (Version 2)

Vitotronic 300 GW2

What is going on

Remote controls and additional KM BUS participants are connected through an on-site terminal box.

Check in this order

  1. Install a terminal box on site.
  2. Connect the control unit to the terminal box.
  3. Connect the remote control units and the further BUS participants through the terminal box, following the diagram.
  4. Keep each branch to the terminal box to a maximum of 15 m / 50 ft.
  5. Keep the total length of all KM BUS cables to a maximum of 50 m / 164 ft.

Applies to: Several remote controls plus additional KM BUS participants

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 300, Model GW2 installation and service instructions, p. 111. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.