Zoning with circulators, two zones plus DHW piped to boiler

SlimFit Series 2

What is going on

Two space heating zones on INPUT 2 and INPUT 3, with a DHW aquastat on INPUT 1. INPUT 1 is assigned to PRIORITY 1 (DHW) and INPUTs 2 and 3 stay on PRIORITY 2.

Check in this order

  1. Wire the space heating thermostats to INPUT 2 and INPUT 3.
  2. Wire the DHW aquastat to INPUT 1.
  3. Keep INPUTs 2 and 3 on PRIORITY 2 and choose the matching space heating system type.
  4. Assign INPUT 1 to PRIORITY 1 (factory default for DHW).
  5. Use the factory DHW defaults or adjust them for the application.

Applies to: SF1000L/R, SF1500L/R, SF2000L/R

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SlimFit Series 2 Boiler Manual 550-100-561/1225, p. 60. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.