Viessmann · Boiler troubleshooting

Connect gateway to Vitotronic control over LON and BACnet/IP

Versatronik 585

What is going on

Wire the gateway to the boiler control and the building network. Use the connection diagram that matches the control and supply voltage.

Check in this order

  1. Make sure the LON communication card is installed in the control. Refer to the boiler or system control manual.
  2. Plug the supplied 3 ft (91 cm) CAT-5 cable into the RJ45 socket on the control and the other end into the RJ45 socket inside the Versatronik 585 gateway.
  3. Plug the BACnet/IP RJ45 communication cable from the building management system into the gateway.
  4. For 120 VAC gateways, connect the plug-in power cord.
  5. For 24 VAC gateways, connect a field-supplied 24 VAC power supply to the gateway.
  6. On the Vitotronic 300-K MW2C, the communication card is required for Vitocontrol-S and the MW2C for Vitodens B2HA boilers.

Applies to: Vitotronic 300 GW5B, GW6B (single and cascade), Vitotronic 300-K MW2C (Vitodens 200, B2HA)

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Versatronik 585 and 585D BACnet IP gateway manual, p. 8. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.