Viessmann · Boiler troubleshooting

Remove the hydraulic unit (B1HE/KE 150/199)

Vitodens 100-W B1HE/B1KE

What is going on

Procedure to pull the hydraulic unit for repair on the 150 and 199 models. Install in reverse order.

Check in this order

  1. Remove the control unit.
  2. Loosen the union nut on the gas pipe. Hold the union nut with an open-ended wrench so the gas pipe is not damaged (two-handed method).
  3. Remove the burner.
  4. Pull off the clip and remove the flow switch.
  5. Pull off the clips and move the supply pipe toward the front to remove it. Use new cable ties to secure the clips on refitting.
  6. Remove the screws on the hydraulic plate at the bottom of the boiler.
  7. Undo the union nut of the boiler pump.
  8. Remove the hydraulic unit.
  9. Refit in reverse order. Check the dual sensor for leaks before returning to service.

Applies to: B1HE/KE 150/199

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 100-W B1HE/B1KE installation manual, p. 88. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.