Viessmann · Boiler troubleshooting
Remove the hydraulic unit (B1HE/KE 150/199)
What is going on
Procedure to pull the hydraulic unit for repair on the 150 and 199 models. Install in reverse order.
Check in this order
- Remove the control unit.
- Loosen the union nut on the gas pipe. Hold the union nut with an open-ended wrench so the gas pipe is not damaged (two-handed method).
- Remove the burner.
- Pull off the clip and remove the flow switch.
- Pull off the clips and move the supply pipe toward the front to remove it. Use new cable ties to secure the clips on refitting.
- Remove the screws on the hydraulic plate at the bottom of the boiler.
- Undo the union nut of the boiler pump.
- Remove the hydraulic unit.
- Refit in reverse order. Check the dual sensor for leaks before returning to service.
Applies to: B1HE/KE 150/199
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 100-W B1HE/B1KE installation manual, p. 88. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.