Pre-start checklist before powering the boiler
What is going on
Final checks to complete before applying power.
Check in this order
- Read the instructions to set up the control.
- Verify the boiler model is set correctly in the control and displays correctly.
- Verify the boiler and system are full of water and components are set for operation.
- Verify the condensate trap is full of water.
- Verify electrical connections are correct, secure and sealed at cabinet openings.
- Inspect vent and air piping for corrosion, damage or sagging and confirm they are intact and installed per the manual.
- Check water piping and DHW piping (combi models) for leaks and vent remaining air from manual vents.
- Check all vent and air piping connections for a gas-tight seal.
Applies to: ECO Tec Series 3 80/110/150/199
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: ECO Tec Series 3 Condensing Gas Boiler Boiler Manual, p. 133. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.