NTI · Boiler troubleshooting
Venting below grade and outdoor vent piping
What is going on
Vent pipe that leaves the building below grade, or runs outside the wall before it terminates, has tighter limits than a normal indoor run. Before touching anything, confirm exactly which section of the vent sits outdoors and how much of it counts toward the total vent length. These limits apply to the NTI TRX150.
Likely causes
- Vent exits the foundation below grade and ground water or soil can reach the penetration
- Long outdoor run exposed to cold, so condensate can freeze or pool in the pipe
- Unsupported or level outdoor pipe that sags and traps condensate
Check in this order
- Excavate down to the point where the pipes exit so you can see the whole penetration.
- Seal the wall fully where the pipes pass through.
- Secure the exhaust and intake to the side of the building above grade.
- Keep all the normal termination clearances.
- Limit piping outside the building to 20 ft, and include that length in the total vent length.
- Support the outdoor pipe every 24 in.
- Slope the exhaust and intake back toward the boiler at 1/2 in per linear foot so condensate drains to the boiler.
Applies to: Below grade and outdoor vent runs
More boiler guides
Related
NTI error codes · NTI parts · NTI tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: NTI TRX150 manual, p. 42. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.