Boiler and system circulator relay requirement
What is going on
An external relay with external power is required for the boiler circulator when its load exceeds 2.2 A FLA, 3.6 A locked rotor, or 16.4 A inrush. An external relay is also required for a system circulator above 2.0 A FLA.
Likely causes
- Boiler circulator load above 2.2 A FLA
- Boiler circulator locked rotor above 3.6 A
- Boiler circulator inrush above 16.4 A
- System circulator load above 2.0 A FLA
Check in this order
- Check the boiler circulator FLA, locked rotor and inrush against the limits.
- Check the system circulator FLA against the 2.0 A limit.
- If any limit is exceeded, provide an external relay and external power to that circulator.
Applies to: Boiler and system circulators in multi-boiler installs
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Series 2 Condensing Gas Boiler Advanced Manual, p. 27 (also p. 32). Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.