Weil-McLain · Boiler troubleshooting

Boiler and system circulator relay requirement

Evergreen Series 2

What is going on

An external relay with external power is required for the boiler circulator when its load exceeds 2.2 A FLA, 3.6 A locked rotor, or 16.4 A inrush. An external relay is also required for a system circulator above 2.0 A FLA.

Likely causes

  • Boiler circulator load above 2.2 A FLA
  • Boiler circulator locked rotor above 3.6 A
  • Boiler circulator inrush above 16.4 A
  • System circulator load above 2.0 A FLA

Check in this order

  1. Check the boiler circulator FLA, locked rotor and inrush against the limits.
  2. Check the system circulator FLA against the 2.0 A limit.
  3. If any limit is exceeded, provide an external relay and external power to that circulator.

Applies to: Boiler and system circulators in multi-boiler installs

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Series 2 Condensing Gas Boiler Advanced Manual, p. 27 (also p. 32). Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.