Lighting and shutting off gas to the appliance (label procedure)
What is going on
Label procedure for the gas supply. The appliance has no pilot; it uses an electronic ignition. Never light the burner by hand and never use tools on the gas control knob.
Check in this order
- Before operating, smell all around the appliance, including near the floor, for gas.
- If gas is smelled, do not light anything, do not touch electrical switches, and leave the area to call the gas supplier from outside.
- Set the thermostat or control to its lowest setting.
- Turn off all electric power to the appliance.
- Close the main manual gas shut-off valve.
- Wait five minutes to clear any gas, then smell again near the floor.
- Open the main manual gas shut-off valve.
- Turn on electric power to the appliance.
- Set the thermostat or control to the desired setting.
- If the appliance will not run, shut off gas as below and call a service technician or the gas supplier.
- To shut off gas set the control to lowest, turn off electric power if service is needed, then close the main manual gas shut-off valve.
- Do not use the appliance if any part has been under water; have a qualified technician inspect it and replace the affected control and gas control parts.
Applies to: Vitodens 200-W B2HB 19 to 125
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 200-W B2HB 19 to 125 service instructions, p. 103. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.