Viessmann · Boiler troubleshooting

Lighting and shutting off gas to the appliance (label procedure)

Vitodens 200-W

What is going on

Label procedure for the gas supply. The appliance has no pilot; it uses an electronic ignition. Never light the burner by hand and never use tools on the gas control knob.

Check in this order

  1. Before operating, smell all around the appliance, including near the floor, for gas.
  2. If gas is smelled, do not light anything, do not touch electrical switches, and leave the area to call the gas supplier from outside.
  3. Set the thermostat or control to its lowest setting.
  4. Turn off all electric power to the appliance.
  5. Close the main manual gas shut-off valve.
  6. Wait five minutes to clear any gas, then smell again near the floor.
  7. Open the main manual gas shut-off valve.
  8. Turn on electric power to the appliance.
  9. Set the thermostat or control to the desired setting.
  10. If the appliance will not run, shut off gas as below and call a service technician or the gas supplier.
  11. To shut off gas set the control to lowest, turn off electric power if service is needed, then close the main manual gas shut-off valve.
  12. Do not use the appliance if any part has been under water; have a qualified technician inspect it and replace the affected control and gas control parts.

Applies to: Vitodens 200-W B2HB 19 to 125

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 200-W B2HB 19 to 125 service instructions, p. 103. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.