Weil-McLain · Boiler troubleshooting
Annual startup and general maintenance checklist
What is going on
Service technician checklist for the yearly startup.
Check in this order
- Review reported problems and inspect the interior. Clean and vacuum if needed. Do not use solvents.
- Clean the base collector and condensate trap, then refill the trap with fresh water.
- Check for water, gas, flue and condensate leaks.
- Check system water chemistry, inhibitor level and antifreeze concentration if used.
- Verify flue and air lines are in good condition and sealed.
- Check system water pressure, piping and expansion tank.
- Check control settings.
- Clean the ignition electrode with steel wool and reposition it. Check ignition and ground wiring and all connections.
- Run the startup checkout and performance verification (page 83 onward).
- Check flame appearance (stable, uniform) and flame signal (Figure 81).
- Clean the heat exchanger if flue temperature is more than 54 F above return water temperature.
- Inspect the jacket front door gaskets and replace if needed.
- If combustion or performance points to a need, clean the heat exchanger, remove and clean the burner with compressed air only, and vacuum the blower.
- Review the findings with the owner.
Applies to: SlimFit 550 and 750 Series 3
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SlimFit series3 commercial gas-fired water boiler boiler manual, p. 90. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.