Weil-McLain · Boiler troubleshooting
Check burner flame
What is going on
Inspect the flame through the observation window at high and low fire.
Likely causes
- Dirty or blocked burner
- Combustion out of adjustment
Check in this order
- Inspect the flame through the window at high fire and at low fire (procedure p. 133).
- If flame is poor, check combustion values.
- If combustion is correct, turn off the boiler and let it cool.
- Remove the burner and clean it with a vacuum or compressed air (do not use compressed air indoors).
- Remove the cover plate to access the burner (p. 151).
- If replacing the burner, make sure the burner gasket is in good condition and correctly placed.
- Restart and inspect again at high and low fire.
- If flame is still poor and combustion is correct, get a replacement burner from WM Technologies.
Applies to: ECO Tec Series 3 gas boilers
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: ECO Tec series 3 boiler manual, p. 142. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.