Viessmann · Boiler troubleshooting

Check and adjust CO2 at upper heating input

Vitocrossal 200 CM2

What is going on

Set the boiler to full load and adjust CO2 with the gas valve adjusting screw.

Check in this order

  1. Press the Y E button until the service display reads 100 (100 %).
  2. Measure CO2 at the flue pipe.
  3. If CO2 is outside the table range, remove cap B.
  4. Turn adjusting screw A with a 3 mm Allen key in small steps. Clockwise lowers CO2 (less gas). Counter-clockwise raises CO2 (more gas).
  5. Record the actual value on the maintenance record (page 64).

Applies to: Vitocrossal 200 CM2 186 to 311

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 16. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.