Connecting a mixing valve actuator
What is going on
A 120V or 24V valve adaptor on the DIN rail links the control to the mixing valve actuator. Power to the control must be off during the work.
Check in this order
- Disconnect power to the control.
- Install a 120V or 24V valve adaptor on the DIN rail inside the connection enclosure.
- Insert the gS plug into the gS socket on the Vitotronic control.
- Fasten the cable with a tie.
- Connect the black wire of the adaptor to terminal 8, 9 or 10 on the DIN rail.
- Connect the valve actuator wires to the adaptor terminals.
- Refer to the mixing valve adaptor installation instructions.
Applies to: Vitotronic 200-H HK1B, heating circuits 1 to 3 mixing valves
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 200-H, HK1B Installation and Service Instructions, p. 19. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.