Removing and cleaning the brazed plate heat exchanger
What is going on
The gas valve does not need to come off to remove the brazed plate heat exchanger.
Likely causes
- Scale deposits in the brazed plate heat exchanger
Check in this order
- Remove the two Allen head bolts with a 4mm Allen wrench.
- Push the brazed plate back away from the manifolds to clear the bolt bosses.
- Slide the brazed plate up and to the left and remove it from the boiler.
- Immerse the brazed plate in a chemical bath for a time shorter than the maximum given on the chemical data sheet.
- Recover the chemical into suitable containers for disposal.
- Flush the brazed plate with potable water and repeat if necessary.
- Reinstall in the same orientation.
Applies to: 80/110/150/199 Series 3
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: ECO Tec series 3 boiler manual, p. 156. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.