Weil-McLain · Boiler troubleshooting

Removing and cleaning the brazed plate heat exchanger

ECO Tec Series 3

What is going on

The gas valve does not need to come off to remove the brazed plate heat exchanger.

Likely causes

  • Scale deposits in the brazed plate heat exchanger

Check in this order

  1. Remove the two Allen head bolts with a 4mm Allen wrench.
  2. Push the brazed plate back away from the manifolds to clear the bolt bosses.
  3. Slide the brazed plate up and to the left and remove it from the boiler.
  4. Immerse the brazed plate in a chemical bath for a time shorter than the maximum given on the chemical data sheet.
  5. Recover the chemical into suitable containers for disposal.
  6. Flush the brazed plate with potable water and repeat if necessary.
  7. Reinstall in the same orientation.

Applies to: 80/110/150/199 Series 3

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ECO Tec series 3 boiler manual, p. 156. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.