Weil-McLain · Boiler troubleshooting
Gas valve throttle and offset adjustment
What is going on
Adjust only as needed to meet Table 16. Confirm the correct low fire RPM before touching the offset screw. Adjust in small steps. Only a qualified technician with calibrated combustion instruments should do this.
Likely causes
- Difficult ignition
- Poor flame stability at low fire
- Combustion noise
- High CO
Check in this order
- Take combustion readings at both high and low fire (Figure 71).
- At high fire, check blower RPM against Table 18 on page 117.
- At high fire, remove the top cover of the gas valve and use a 4 mm Allen wrench on the throttle screw. If CO2 is high, turn clockwise in small steps. If CO2 is low, turn counterclockwise in small steps.
- Allow 20 to 30 seconds to stabilize, then read again. Repeat until CO2 is correct and confirm CO is within limits.
- Reinstall the gas valve top cover.
- At low fire (0%), let the boiler stabilize and confirm RPM against Table 18.
- Remove the T40 Torx cap over the offset screw. If CO2 is high, turn the offset screw counterclockwise in very small steps. If CO2 is low, turn it clockwise.
- Wait for stabilization (a few minutes), repeat until CO2 is correct and CO is within limits.
- Reinstall the T40 Torx cap.
- Turn the boiler off and back on, then recheck high and low fire CO2 and CO.
Applies to: Gas valves on SVF 500/600 Series 1 boilers
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SVF 500/600 Series 1 Boiler Manual, p. 99-100. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.