Connect combustion air device adaptor (single boiler)
What is going on
Wire a combustion air blower to the Vitotronic through the adaptor board in the connection enclosure.
Check in this order
- Disconnect power to the control and burners.
- Mount the combustion air device adaptor (PN 7134 563) on the DIN rail inside the connection enclosure, following the adaptor manual.
- Remove the jumper between terminals 16 and 17.
- Connect wire BK2 to terminal 16 and BK3 to terminal 17. Do not reverse them.
- Wire the blower motor, the normally open proving switch (120 VAC rated) and the 120 VAC supply as shown in the diagram.
- Provide disconnect means and overcurrent protection as local codes require.
- Confirm the blower is suitable for this application (see ratings table).
Applies to: Single boiler with combustion air blower
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 100 GC1 / 300-K MW1S installation, p. 40. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.