Weil-McLain · Boiler troubleshooting

Gas valve throttle screw adjustment at high fire

SlimFit Series 2

What is going on

Only a qualified technician with calibrated combustion instruments may adjust the gas valve. Adjust only as needed to reach the CO2 values in the acceptable values table. Propane is especially sensitive.

Likely causes

  • High or low CO2 at high fire
  • Difficult ignition, unstable low fire, combustion noise or high CO

Check in this order

  1. Force high fire in Manual test mode and let the boiler stabilise until the high fire RPM is reached.
  2. Take a CO2 reading.
  3. Remove the blue cover over the throttle screw opening.
  4. Make only 1/8 turn adjustments with a 3 mm Allen wrench.
  5. If CO2 is high, turn the throttle screw clockwise to lower input.
  6. If CO2 is low, turn the throttle screw counterclockwise to raise input.
  7. Allow the boiler to stabilise and read again after each adjustment until the target is reached.
  8. Reinstall the blue cover.

Applies to: SlimFit Series 2 gas valve

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SlimFit Series 2 boiler manual 550-100-561/1225, p. 82. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.