Check expansion tank(s)

ECO Tec Series 3

What is going on

Confirm the expansion tank is sized and charged correctly.

Likely causes

  • Waterlogged closed-type tank
  • Diaphragm or bladder membrane damaged
  • Tank undersized for the system
  • Relief valve weeping frequently

Check in this order

  1. Identify the tank type (closed-type or diaphragm/bladder).
  2. Diaphragm or bladder tank check that tank size is adequate; if not, add tanks. If size is correct, remove it and check charge pressure (usually 12 PSIG residential). If it will not hold pressure, replace the tank.
  3. Closed-type tank check fill level per the fitting manufacturer; if correct, check tank size and replace with a larger tank if needed. If not waterlogged, install a tank fitting (for example Tank-trol or Taco-trol).
  4. Do not use automatic air vents on closed-type tank systems.

Applies to: ECO Tec Series 3 boiler systems

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ECO Tec series 3 boiler manual, p. 141. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.