Weil-McLain · Boiler troubleshooting
Check expansion tank(s)
What is going on
Confirm the expansion tank is sized and charged correctly.
Likely causes
- Waterlogged closed-type tank
- Diaphragm or bladder membrane damaged
- Tank undersized for the system
- Relief valve weeping frequently
Check in this order
- Identify the tank type (closed-type or diaphragm/bladder).
- Diaphragm or bladder tank check that tank size is adequate; if not, add tanks. If size is correct, remove it and check charge pressure (usually 12 PSIG residential). If it will not hold pressure, replace the tank.
- Closed-type tank check fill level per the fitting manufacturer; if correct, check tank size and replace with a larger tank if needed. If not waterlogged, install a tank fitting (for example Tank-trol or Taco-trol).
- Do not use automatic air vents on closed-type tank systems.
Applies to: ECO Tec Series 3 boiler systems
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: ECO Tec series 3 boiler manual, p. 141. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.